The Letter H – Getting Started
Hydronic Design, Primary-Secondary Piping, Training & Education
Primary-secondary piping doesn't have to be mysterious. Drawing a capital H captures every P-S connection's four arms and decoupler pipe, making it easy to map out flow rates, temperatures, and blending direction for both design and troubleshooting purposes.
Check, Check, Double-Check
Best Practices, Commissioning, Troubleshooting
A practical troubleshooting checklist developed from years of field experience — covering power, gas, rotation, valve positions, strainers, flues, and more. Running through the basics before making a site visit saves time for everyone and often reveals embarrassingly obvious problems.
RCMP Prison Toilets won’t
Installation Tips, Plumbing, Troubleshooting
Prison flush valves that wouldn't work properly pointed to a water pressure problem. The cause was buried underground — a hot tap connection where the installer had only drilled the small pilot hole instead of the full-diameter cutter hole, restricting the water supply to a quarter-inch opening.
Upside Down (and Far Away)
Controls & Thermostats, Residential Heating, Troubleshooting
A mother's condo heating system got hotter the more she turned it down. The problem: her brother had replaced the thermostat with a direct-acting model, but hydronic zone valves are normally open and require a reverse-acting thermostat. Diagnosed from 800 kilometres away over the phone.
Injection Issues
Boilers, Primary-Secondary Piping, Troubleshooting
A boiler short-cycling like it was possessed turned out to be an injection pump issue in a primary-secondary radiant floor system. The globe valve in the injection return was wide open, causing the radiant supply to match boiler temperature, which repeatedly triggered the controller to shut down and restart the boiler.
Blow Me Down – 3- Phase Motor
Motors & Electrical, Troubleshooting, Ventilation
When an inline vane axial return fan wouldn't produce airflow, the boss climbed a ladder and held cardboard over a hole the contractors had cut — and got blown off the ladder. The fan was rotating backwards, a common 3-phase motor wiring issue fixed simply by swapping two of the leads.
A Metric Bite in the Butt & Jerry’s Pump laws
Flow Control, Pumps & Circulators, Troubleshooting
A domestic hot water recirculation pump showed almost no differential pressure — which actually meant too much flow, not too little. The cause: a metric conversion slip during submittals supplied 10 GPM flow limiters instead of 1.0 GPM, allowing the pump to drift nearly off its curve.